What size and power a garage mini split needs
A garage is sized like any other room, with two things to check: its ceiling height and its insulation. Then the power question decides which models are easy to install.
Size it
Start with the floor area and ENERGY STAR’s table. A 20 by 20 ft garage is 400 sq ft, which reads 10,000 BTU, on an 8 foot ceiling.
Garage ceilings can be higher than 8 feet. Senville adds 10 percent for every 2 feet over 8 feet, so a 10 foot ceiling gives 11,000 BTU for the same garage. Senville’s guide also lists 15 to 20 percent more for poor insulation. If yours is poorly insulated, for this example, 15 to 20 percent more is about 12,650 to 13,200 BTU. The mini split tool applies the ceiling rule, and leaves insulation for you to add.
If the garage is used in ways the table does not cover, ask a contractor for a load calculation.
Power
In the two lines we checked, every model above 12,000 BTU runs on 230 volts, and some 12,000 BTU models run on 115 volts. From the makers' own brochures:
| Model | Supply | Maker’s minimum circuit ampacity | Maximum circuit protection |
|---|---|---|---|
| MRCOOL DIY 12,000 BTU | 115 V | 19 A | 25 A |
| Pioneer Diamante Pro 12,000 BTU | 115 V | 17 A | 25 A |
| Pioneer Diamante Pro 12,000 BTU | 230 V | 11 A | 15 A |
| MRCOOL DIY 18,000 BTU | 230 V | 18 A | 30 A |
Pioneer’s 12,000 BTU model lists 17 A on 115 volts and 11 A on 230 volts. Check what is in your panel, and have an electrician size the circuit and the disconnect. MRCOOL’s own sheet says a certified electrician supplies power from a disconnect, and Pioneer’s manual says a licensed electrician installs the wiring.
Where the units go
The indoor unit mounts high on a wall. MRCOOL’s manual asks for 5.9 in above it and 4.75 in at each side. Pioneer’s manual asks for the bottom of the indoor unit to be at least 6 feet above the floor, with ideally 8 inches above it and at least 4 to 6. The outdoor unit needs 12 in behind it on the ground for MRCOOL (6 in on a bracket), 12 in on its left, 24 in on its right, 24 in above and 79 in in front. The line set between them has a longest run: 82 ft for MRCOOL’s 12,000 BTU model and 50 ft for Pioneer’s.
Check models against your wall
Facts read on each maker’s own documents on 19 November 2026.